District Heating from Data Center Heat, Odense

In Odense, Denmark, heat pumps lift waste heat from Meta's data center to warm about 11,000 homes. How heat is collected from an air-cooled data center, and how the project grew.

case-study

Earlier in this series we saw that data center waste heat is low in temperature, and that heat from air-cooled data centers in particular is hard to reuse. So can data center waste heat really warm people’s homes?

In Odense, Denmark, it already does. Heat pumps lift the lukewarm heat from Meta’s data center to warm about 11,000 homes. This post looks at how Odense uses data center waste heat for district heating, and how the project has grown.

The Odense data center waste heat project

Item Details
Data center Meta’s Odense data center (Denmark)
Heat taken by Odense district heating (Fjernvarme Fyn)
Heat supply since 2020
Heat pump output About 45MW
Supply temperature 70–75°C
Homes warmed About 11,000 (as of January 2025)

Collecting heat from an air-cooled data center

Meta’s Odense data center is air-cooled, meaning it cools its servers with outdoor air. The air leaving an air-cooled data center is only lukewarm and hard to use as it is, so in Odense the heat is first transferred to water and then raised in temperature by heat pumps.

※ Air cooling: cooling servers by blowing cool air over them
※ Liquid cooling: cooling servers with a liquid such as water

How waste heat from Meta's Odense data center reaches district heating. Outdoor air cools the servers, and the air warmed by the servers heats cooling water in water coils. The warmed water flows to Fjernvarme Fyn's heat pump plant, and the water that has given up its heat returns to the data center. Ammonia heat pumps running on renewable electricity raise the heat to 70–75°C and send about 45MW into the district heating network, warming about 11,000 homes

Fjernvarme Fyn invested in and operates the heat pump plant, and the heat pumps run on renewable electricity.

The original plan and today

When Meta announced the plan in 2018, it expected to recover 100,000MWh of heat a year, enough to warm 6,900 homes. Heat supply began in 2020, and in the same year Odense’s district heating company began planning to expand the plant.

As of January 2025, waste heat from Meta’s data center alone supplies district heating to about 11,000 homes, well beyond the original plan.

The bottom line

Odense shows that even lukewarm heat from an air-cooled data center can heat a city once heat pumps raise its temperature. A heat supply first planned for 6,900 homes now warms about 11,000.

Heat that was once thrown away can warm a city when it is matched with the right place and the right way to use it. GIGAette’s IsoTES® is a constant-temperature thermal storage system that charges from whichever heat source fits — waste heat, renewable electricity or grid power — and releases the stored heat at a steady temperature.

If you would like to work out where the heat from your facility could be used, request a technical meeting.


Sources

Share this article

Frequently asked questions

How many homes does the Odense data center's waste heat warm?

According to Fjernvarme Fyn, Odense's district heating company, waste heat from Meta's data center alone supplied district heating to about 11,000 homes as of January 2025.

Can waste heat from an air-cooled data center be used?

Yes. Meta's Odense data center cools its servers with outdoor air. The air warmed by the servers passes over water coils to collect its heat, and heat pumps raise it to 70–75°C before it goes into the district heating network.

Since when has the Odense data center's heat been used for district heating?

The heat recovery plant was ready to operate in late 2019, and it has supplied heat to the district heating network since 2020.