Europe's Rules on Data Center Waste Heat

Europe has begun regulating data center waste heat. How much waste heat EU data centers reuse today, the EU data center label and the duty to use waste heat.

basics

The previous post looked at how South Korea has used data center waste heat so far. Europe has gone a step further and begun regulating it.

From 2027, the EU plans to issue every data center an energy efficiency label that also shows whether it is ready to supply its waste heat. Even if a data center does not supply heat today, the label will show whether it has the equipment to do so. This post covers how much waste heat European data centers reuse today and the EU rules on data center waste heat.

Waste heat reuse at European data centers today

The European Commission estimates that reusing an average of half of European data centers’ waste heat could cover the heating demand of almost 4 million European households. In practice, however, little of that heat is reused yet.

Since 2024, the EU has required data centers with at least 500kW of IT capacity to report their energy use, waste heat reuse and other figures every year. Of the 770 data centers in the first round of reporting in 2024, 67 reported reusing any waste heat at all, and about 1.8% of the heat produced by data centers was reused. The report notes, however, that some computed values seemed unrealistically high, so this figure may not fully represent waste heat reuse across the EU.

The EU report gives these reasons.

Factor Details
Readiness Facilities differ in how well they are equipped to supply waste heat outside
Cost Raising the heat’s temperature and delivering it to users takes investment
Timing The heat on offer comes in an irregular pattern or not when it is needed
Demand There is no one nearby to take the heat

The report finds it difficult to set a target for the share of waste heat reused, because reuse is only possible where there is local demand for the heat and local infrastructure to deliver it. It notes that reuse usually does not pay off for small data centers, that in warmer regions data centers need cooling when homes and office buildings have very low to zero heating demand, and that even in regions with high heating demand, seasonal swings in demand remain a major difficulty.

EU rules on data center waste heat

The EU Energy Efficiency Directive (2023) requires data centers with a total rated energy input above 1MW to use their waste heat, unless they show that this is not technically or economically feasible. Germany set waste heat reuse shares for new data centers in its 2023 Energy Efficiency Act and is now discussing amendments to the law.

※ Energy Efficiency Directive: EU energy efficiency rules that member states must write into their national law

On 21 September 2026, the European Commission put forward a rating scheme for data centers. The scheme will enter into force after review by the European Parliament and the Council and publication in the Official Journal. From 2027, every data center that has reported to the EU database will then automatically receive an electronic label each year, showing its energy efficiency class and water use class along with whether it is waste heat reuse ready (yes/no). The labels will be publicly available in the EU database.

Here, waste heat reuse ready means having equipment such as heat exchangers, dedicated piping and heat meters so that the data center can supply waste heat outside its boundary. A data center counts as ready even without a heat pump to raise the heat’s temperature or an external heat network. Whether or not a data center reuses any waste heat today, it must report whether it is ready.

※ Data center label: like the energy efficiency rating on a fridge or air conditioner, a label that shows a data center’s energy efficiency class and other ratings

The EU is also considering minimum performance standards for data centers. It is collecting views until 14 December 2026, and the Commission has listed waste heat reuse among the example areas, together with energy efficiency and water use.

Where data center waste heat rules are heading

Of the four reasons for low waste heat reuse above, the one the EU label addresses directly is readiness, because the label shows whether a data center has the equipment to supply its waste heat.

One thing rules alone cannot easily solve is timing. When heat is produced at different times from when it is needed, having the equipment in place does not close that gap. Storing heat and drawing on it when needed can narrow it.

The bottom line

The EU requires data centers above 1MW to use their waste heat in principle, and from 2027 it plans to make public whether each data center has the equipment to supply its waste heat. Even data centers that do not yet supply heat will have their readiness shown, and minimum performance standards are also under consideration.

GIGAette’s IsoTES® is a constant-temperature thermal storage system that charges from whichever heat source fits — waste heat, renewable electricity or grid power — and releases the stored heat at a steady temperature.

If you would like to work out where the heat from your facility could be used, request a technical meeting.


Sources

Share this article

Frequently asked questions

How are data center energy efficiency classes defined?

The EU data center label sorts data centers into seven classes by PUE, from A (1.15 or less) to G (above 1.9). PUE is the total energy a data center uses divided by the energy its IT equipment uses, so the closer it is to 1, the more efficient the data center. The average PUE of data centers reporting in the EU in 2024 was 1.36.

Can small data centers or ones still under construction get a label?

Yes, once the rating scheme enters into force. Data centers with less than 500kW of IT capacity, or ones not yet in operation, can join the scheme voluntarily. A data center not yet in operation reports the performance values it is designed to reach two years after starting operation, then reports actual values once it is running.

Does running a heat pump to reuse waste heat worsen a data center's efficiency class?

The EU rating scheme, not yet in force, has data centers subtract the energy used to raise the temperature of waste heat that is actually reused and reported (heat pumps, heat exchangers, heat network equipment and so on) from their total energy use. That energy is left out when the efficiency class is calculated.