Earlier in this series we looked at Odense, Denmark, where data center waste heat warms about 11,000 homes. So can South Korea use data center waste heat too?
South Korea made a first attempt, but it stalled because the heat’s temperature and price did not work out. Today data centers produce warmer heat, and if places to use that heat are planned nearby from the start, the prospects are better. This post looks at the attempt made in Korea, what made it hard, what has changed since, and how data center waste heat could be used in Korea.
Korea’s attempt to use data center waste heat
In 2012, a telecom company and a district heating operator in Korea first discussed sending data center waste heat into district heating. The plan was to replace the data center’s chillers with heat pumps, raise the heat from cooling the servers to around 75°C, and send it into the district heating network.
The project, however, never got past the discussion stage.
Why using data center waste heat was hard
A 2019 report by the Korea Energy Economics Institute summed up the reasons.
| Issue | Details |
|---|---|
| Temperature | The district heating plant sends 110°C water to homes and takes back the water that has cooled to about 55°C after heating them, then heats it again. Heat at 75°C was too low to send straight to homes, so it could only pre-heat the water returning to the plant |
| Revenue | A district heating plant makes and sells electricity along with heat. Filling part of the heat demand with waste heat means running the plant less, so it sells less electricity |
| Price | The data center side wanted a price that covered its investment and higher power use, the district heating side wanted a lower one, and this gap was the biggest sticking point |
The report also suggested that the project may have struggled because it aimed to replace existing heat sources rather than serve new heat demand. It further found that, as of 2019, Korea had very limited policy support for using data center waste heat.
What has changed for data center waste heat
The biggest change is the temperature of the heat. As AI GPU servers spread, liquid cooling, which cools servers directly with water, is growing fast, and it can recover heat at 45–70°C. That is still below the 110°C sent out by Korea’s combined heat and power district heating, but it is far warmer than heat from air cooling, and with heat pumps it can be used in more places.
※ Liquid cooling: cooling servers directly with a liquid such as water
There is also more heat. The Korea Energy Economics Institute projects that electricity use by Korean data centers will grow from 5.0TWh in 2023 to 13.8TWh in 2030. Almost all of that electricity ends up as heat, so the waste heat grows with it.
A new attempt has also begun. On 24 September 2024, Korea District Heating Corporation, IGIS Asset Management and the Ministry of Trade, Industry and Energy signed an agreement on data center energy efficiency and a low-carbon supply system for district energy. IGIS Asset Management has said that once the system is complete, it plans to reuse waste heat from the data center it is building in Samsong, Goyang, Gyeonggi Province, for nearby district heating. It is still at the planning stage, so it remains to be seen when heat will actually flow.
How data center waste heat could be used in Korea
The 2012 attempt ran into trouble trying to fit waste heat into a district heating system already running on other heat sources. The Korea Energy Economics Institute researchers behind the 2019 report propose discussing data center waste heat from the stage of planning new towns. Existing district heating systems were designed around their original heat sources, they explain, so connecting waste heat later inevitably makes the existing heat production equipment somewhat less efficient.
It also helps for heat users to be close by, because heat is lost as it travels. And residents are open to the idea: a study of a 2021 survey of 538 people found that respondents preferred data center waste heat and water-source heat over heat from waste incineration as sources for district heating.
District heating is not the only nearby user. Abroad, fish farms, greenhouses, swimming pools and wood-drying plants already take data center waste heat, and these uses are usually less seasonal than district heating. If places like these are planned close by when a data center is built, Korea will have more ways to use data center waste heat.
※ Water-source heat: heat held in water such as rivers or sewage
The bottom line
South Korea’s first attempt to use data center waste heat stalled because temperature and price did not work out. Today liquid cooling produces warmer heat, and a new agreement was signed in 2024. If places to use the heat are planned nearby from the start, data center waste heat has plenty of uses — not only district heating but also greenhouses, fish farms and swimming pools.
Using heat that would otherwise be thrown away means matching where heat is produced with where it is used. GIGAette’s IsoTES® is a constant-temperature thermal storage system that charges from whichever heat source fits — waste heat, renewable electricity or grid power — and releases the stored heat at a steady temperature.
If you would like to work out where the heat from your facility could be used, request a technical meeting.
Sources
- A Case Study on the Use of Data Center Waste Heat for District Heating and Cooling and Its Policy Implications — Korea Energy Economics Institute (KEEI), Occasional Research Report 19-01, Oh, S. (2019-08-31, in Korean) — 2012 talks between a telecom company and a district energy operator (chillers replaced with heat pumps, around 75°C, CHP supply 110°C and return 55°C, usable only for return water, lower CHP operation and power sales, price gap the biggest issue, replacing existing heat sources without new demand), about 430MW of Korean data centers giving about 72,000 households by simple calculation (about 5% of 2.8 million district-heated households in 2017), very limited policy support as of 2019, proposals for policy changes and planning at the urban planning stage (policy proposals are the researchers’ personal views)
- Heat Reuse, Sustainable Data Centers Roadmap — Innovation for Cool Earth Forum (ICEF) (2025-10) — liquid cooling recovers heat at 45–70°C, liquid cooling growing fast with GPU-based AI, combining with heat pumps widens possible uses, Green Mountain land-based trout farm in Norway, greenhouses at Luleå University of Technology and the University of Notre Dame, wood pellet drying at EcoDataCenter in Falun, many fish farm, greenhouse and drying uses lack the seasonal constraint of district heating
- Implications of Data Center Growth in the AI Era for Korea’s Energy Consumption — Korea Energy Economics Institute (KEEI), Basic Research Report 2025-09 (2025-12-31, in Korean) — Korean data center electricity use 5.0TWh in 2023, projected 13.8TWh in 2030
- Energy Efficiency through Data Center Waste Heat — Korea Energy Agency, KEA Energy Issue Briefing No. 252 (2024-11-04, in Korean) — agreement of 24 September 2024 between Korea District Heating Corporation, IGIS Asset Management and the Ministry of Trade, Industry and Energy, reuse of data center waste heat for district heating, expansion to biogas and hydrogen production process heat, plan to raise the share of unused heat from 13% to 20% by 2030
- Meta: surplus heat to district heating — Ramboll — Meta’s Odense data center, electric ammonia heat pumps to 70–75°C
- Small but powerful: Tiny data center heats UK swimming pool — AFP, published by Tech Xplore (2023-06-23) — Exmouth leisure centre in the UK heats its indoor pool with heat from a small data center
- Data Center Waste Heat, an Emerging Green Energy Source — IGIS Asset Management UNFOLD (2024-10-07, in Korean) — once the system is complete, waste heat from the data center under construction in Samsong, Goyang, to be reused for nearby district heating
- A Study on Residents’ Acceptance of Unused Heat Energy in District Energy — Won, D. and Oh, S., Environmental and Resource Economics Review, Vol. 32, No. 3 (2023-09, in Korean) — heat loses much in transport so sources should be near demand; in an August 2021 survey (538 people), water-source heat and data center waste heat preferred over incineration heat
- Cover image: AI-generated (colour-adjusted)